Wire & Cable

Southwire wire and cable for residential and light commercial work — building wire, Romex, direct burial, metal clad and data cable, in every common gauge.
The first question is always where it is going, because that decides the type before the gauge:

NM-B (Romex) — dry, indoor, protected locations only. Never underground, never in wet locations, not even in conduit outdoors.
THHN/THWN-2 — in conduit, wet or dry. The inside of outdoor or buried conduit is a wet location by NEC 300.5(B), which is why you need the THWN-2 rating and not plain THHN.
UF-B — direct burial without conduit, sunlight resistant.
MC cable — exposed or concealed indoor runs, and commercial work where NM-B is not permitted.

Then size it. Ampacity comes from NEC Table 310.16, but remember NEC 110.14(C) pulls you back to the 75°C column on ordinary gear, and NEC 240.4(D) caps the breaker at 15, 20 and 30 amps for 14, 12 and 10 AWG regardless. On long runs voltage drop decides, not ampacity.