Short runs are sized from NEC Table 310.16 and that is the end of it. Long runs are different, because resistance in the conductor costs you voltage along the way — and at the far end you can be inside code and still have equipment that runs badly.
What the code actually says
This surprises people: voltage drop is not a hard NEC requirement for most branch circuits. It appears as an informational note to 210.19(A), recommending no more than 3% on a branch circuit and 5% total including the feeder.
It is a recommendation, not a rule — but ignoring it gives you motors that run hot and draw more current, lights that dim when the compressor starts, and electronics that behave oddly. Good practice treats the 3% figure as a design target.
The arithmetic
For a single-phase circuit:
Voltage drop = 2 × K × I × L ÷ CM
- K = 12.9 for copper (21.2 for aluminium)
- I = current in amps
- L = one-way distance in feet
- CM = circular mils of the conductor
Circular mils by size: 14 AWG = 4,110 · 12 AWG = 6,530 · 10 AWG = 10,380 · 8 AWG = 16,510 · 6 AWG = 26,240 · 4 AWG = 41,740 · 2 AWG = 66,360.
What 100 feet does in practice
| Load | Ampacity says | At 100 ft on 240 V | At 100 ft on 120 V |
|---|---|---|---|
| 20 A | 12 AWG | 12 AWG — 1.6%, fine | 12 AWG — 3.3%, marginal |
| 30 A | 10 AWG | 10 AWG — 1.5%, fine | 8 AWG — 10 AWG drops 3.1% |
| 50 A | 8 AWG | 8 AWG — 1.6%, fine | — |
| 60 A | 6 AWG | 6 AWG — 1.2%, fine | — |
| 100 A | 3 AWG | 3 AWG — 1.3%, fine | — |
The pattern worth absorbing: at 240 volts, 100 feet is rarely a problem. At 120 volts it frequently is, because the same drop in volts is twice the percentage of a smaller supply voltage.
That is why long 120 V circuits — a shed light, a well house, outlets at the end of a property — are where people get caught, not the big 240 V feeders.
When the run gets really long
| One-way distance | 20 A at 120 V | 30 A at 240 V | 60 A at 240 V |
|---|---|---|---|
| 50 ft | 12 AWG | 10 AWG | 6 AWG |
| 100 ft | 10 AWG | 10 AWG | 6 AWG |
| 150 ft | 8 AWG | 8 AWG | 6 AWG |
| 200 ft | 6 AWG | 8 AWG | 4 AWG |
| 300 ft | 4 AWG | 6 AWG | 2 AWG |
A shortcut that is close enough
For copper at 3% drop, a rule that works well in the field: multiply amps by one-way feet. If the result exceeds about 600 at 120 V, or 2,400 at 240 V, go up a size from the ampacity minimum.
A 20 amp circuit 100 feet out at 120 V is 2,000 — well over 600, so go up from 12 AWG to 10 AWG. The same 20 amps at 240 V is still 2,000, under 2,400, so 12 AWG holds.
Generators have their own rule
If the run is between a standby generator and its transfer switch, voltage drop is the second consideration. NEC 445.13 requires those conductors to be rated at not less than 115% of the generator nameplate current, which is a different and usually larger figure than the ordinary ampacity table.
We cover that separately in what size wire between a generator and transfer switch.
We stock Southwire THHN/THWN-2 building wire, NM-B Romex and UF-B direct burial cable in every common gauge. Not sure which you need? Tell us the run and the load and a licensed electrician will size it with you.
Frequently Asked Questions
Do I need bigger wire for a 100 foot run?
At 240 volts, usually not — ampacity still governs. At 120 volts, often yes. A 20 amp 120 V circuit at 100 feet drops about 3.3% on 12 AWG, so 10 AWG is the better choice.
Is voltage drop a code requirement?
Not for most branch circuits. NEC 210.19(A) carries an informational note recommending 3% on a branch circuit and 5% overall. It is a design recommendation rather than an enforceable rule, but it is worth following.
How do I calculate voltage drop?
For single phase: VD = 2 × K × I × L ÷ CM, where K is 12.9 for copper, I is amps, L is the one-way distance in feet, and CM is the conductor’s circular mils.