Short runs are sized from NEC Table 310.16 and that is the end of it. Long runs are different, because resistance in the conductor costs you voltage along the way — and at the far end you can be inside code and still have equipment that runs badly.

What the code actually says

This surprises people: voltage drop is not a hard NEC requirement for most branch circuits. It appears as an informational note to 210.19(A), recommending no more than 3% on a branch circuit and 5% total including the feeder.

It is a recommendation, not a rule — but ignoring it gives you motors that run hot and draw more current, lights that dim when the compressor starts, and electronics that behave oddly. Good practice treats the 3% figure as a design target.

The arithmetic

For a single-phase circuit:

Voltage drop = 2 × K × I × L ÷ CM

  • K = 12.9 for copper (21.2 for aluminium)
  • I = current in amps
  • L = one-way distance in feet
  • CM = circular mils of the conductor

Circular mils by size: 14 AWG = 4,110 · 12 AWG = 6,530 · 10 AWG = 10,380 · 8 AWG = 16,510 · 6 AWG = 26,240 · 4 AWG = 41,740 · 2 AWG = 66,360.

What 100 feet does in practice

LoadAmpacity saysAt 100 ft on 240 VAt 100 ft on 120 V
20 A12 AWG12 AWG — 1.6%, fine12 AWG — 3.3%, marginal
30 A10 AWG10 AWG — 1.5%, fine8 AWG — 10 AWG drops 3.1%
50 A8 AWG8 AWG — 1.6%, fine—
60 A6 AWG6 AWG — 1.2%, fine—
100 A3 AWG3 AWG — 1.3%, fine—
Percentages are one-way 100 ft, copper, at the stated load.

The pattern worth absorbing: at 240 volts, 100 feet is rarely a problem. At 120 volts it frequently is, because the same drop in volts is twice the percentage of a smaller supply voltage.

That is why long 120 V circuits — a shed light, a well house, outlets at the end of a property — are where people get caught, not the big 240 V feeders.

When the run gets really long

One-way distance20 A at 120 V30 A at 240 V60 A at 240 V
50 ft12 AWG10 AWG6 AWG
100 ft10 AWG10 AWG6 AWG
150 ft8 AWG8 AWG6 AWG
200 ft6 AWG8 AWG4 AWG
300 ft4 AWG6 AWG2 AWG
Sized to keep voltage drop at or under 3%. Always at least the ampacity minimum.

A shortcut that is close enough

For copper at 3% drop, a rule that works well in the field: multiply amps by one-way feet. If the result exceeds about 600 at 120 V, or 2,400 at 240 V, go up a size from the ampacity minimum.

A 20 amp circuit 100 feet out at 120 V is 2,000 — well over 600, so go up from 12 AWG to 10 AWG. The same 20 amps at 240 V is still 2,000, under 2,400, so 12 AWG holds.

Generators have their own rule

If the run is between a standby generator and its transfer switch, voltage drop is the second consideration. NEC 445.13 requires those conductors to be rated at not less than 115% of the generator nameplate current, which is a different and usually larger figure than the ordinary ampacity table.

We cover that separately in what size wire between a generator and transfer switch.

We stock Southwire THHN/THWN-2 building wire, NM-B Romex and UF-B direct burial cable in every common gauge. Not sure which you need? Tell us the run and the load and a licensed electrician will size it with you.

Frequently Asked Questions

Do I need bigger wire for a 100 foot run?

At 240 volts, usually not — ampacity still governs. At 120 volts, often yes. A 20 amp 120 V circuit at 100 feet drops about 3.3% on 12 AWG, so 10 AWG is the better choice.

Is voltage drop a code requirement?

Not for most branch circuits. NEC 210.19(A) carries an informational note recommending 3% on a branch circuit and 5% overall. It is a design recommendation rather than an enforceable rule, but it is worth following.

How do I calculate voltage drop?

For single phase: VD = 2 × K × I × L ÷ CM, where K is 12.9 for copper, I is amps, L is the one-way distance in feet, and CM is the conductor’s circular mils.