CAT5e and CAT6 data cable, 4-pair unshielded twisted pair, solid bare copper, riser rated.
If you are opening walls, pull CAT6. Both do gigabit to 100 metres, but CAT6 runs 250 MHz against 100 MHz, has a thicker 23 AWG conductor and a spline separating the pairs for lower crosstalk, and is rated for 10 gigabit to 55 metres. The cable is a small fraction of the labour and you will not be back in that ceiling for twenty years.
CMR riser rating is a code requirement, not a marketing tier. CMR resists carrying flame vertically between floors and is required in shafts and floor-to-floor runs. If the cable is going into a return-air plenum you need CMP instead — CMR is not a substitute. Ask us and we will get it.
Pulling it well matters more than people expect: keep 12 inches from parallel power cable, cross at 90 degrees, never exceed 25 lbf of tension, keep the bend radius at four times the diameter, and keep the twist to within half an inch of the punch-down.