Short answer: most American homes land on 18kW to 22kW for whole-house backup. The honest version is that it depends on whether you want the whole house or just the circuits that matter, and on one load above all others — your air conditioner.
There are two ways to size a generator
Whole house means the generator carries everything, and you never think about what is running. Managed or essential circuits means you cover heat, water, refrigeration, and some outlets, and the rest stays dark.
Whole-house costs more up front. Essential-circuit costs less and is perfectly livable. Most people who regret their choice regret going too small, because the cost gap between 18kW and 22kW is far smaller than the cost of replacing an undersized unit two years later.
Your air conditioner decides most of this
A central AC compressor draws a large surge on startup — several times its running current, for a moment. That surge is what sizes generators in practice.
A 3-ton unit is usually comfortable on an 18kW. A 5-ton unit, or two systems, pushes you to 22kW or above. Many Generac air-cooled units ship with soft-start-friendly load management that sheds the AC briefly when something bigger kicks on, which can let a smaller generator cover a larger house than raw math suggests.
What actually matters in the calculation
- Square footage — a rough proxy, not an answer
- Electric vs gas for heat, water heater, range and dryer — an all-electric home needs materially more generator
- Well pump — another big starting load that catches people out
- AC tonnage and how many systems
- Service size — 200A service with heavy loads rarely sits happily behind a 14kW
Rough starting points
| Home | Typical fit |
|---|---|
| Under 1,500 sq ft, gas heat, no well | 10–14kW |
| 1,500–2,500 sq ft, one AC system | 18kW |
| 2,500–3,500 sq ft, or 5-ton AC | 22kW |
| All-electric, two systems, or well pump | 24kW+ |
These brackets are a conversation starter. A 1,800 sq ft all-electric house with a well pump can need more generator than a 3,000 sq ft house on gas.
Natural gas derates
Dual-fuel units produce slightly less output on natural gas than on liquid propane. If you are running natural gas and sizing right at the edge, that difference matters. Check the nameplate rating for your fuel, not the headline number.
The mistake that costs the most
Buying on sticker price alone. The gap between an 18kW and a 22kW is a few hundred dollars. The gap between a correctly sized generator and one that trips under load on the first winter night is the whole installation.
Undersizing also shortens the life of the unit — a generator running at the top of its range constantly works harder than one with headroom.
Not sure? Tell us the house.
Give us square footage, AC tonnage, whether heat and water are gas or electric, and whether there is a well pump. We will tell you the size — and if a smaller unit with load management will do the job, we will tell you that too.
Browse home standby generators, or read what size wire you will need once you have picked one.