Southwire 12 AWG Solid Copper THHN/THWN-2 Building Wire, Black — 500 ft
12 AWG solid copper THHN/THWN-2, black, 500 ft. 90°C wet or dry — good in buried conduit.
Southwire 12 AWG solid copper THHN/THWN-2 building wire in black, on a 500 ft roll. Single conductor, 600 volt, for pulling into conduit, raceway and enclosures.
Why THHN/THWN-2 and Not Just THHN
Most wire sold as THHN is dual-rated, and the second rating is the one that matters outdoors. The print on the jacket tells you what you actually have:
- THHN — 90°C in dry locations only
- THWN — 75°C in wet locations
- THWN-2 — 90°C wet or dry, which is what you want
This is the part people miss: the inside of a conduit run outdoors, or underground, is a wet location by NEC definition — 300.5(B) and 300.9 say so plainly. Plain THHN in a buried conduit is a violation. THWN-2 is not.
Solid or Stranded?
This roll is solid — one single copper conductor. Solid is stiffer, holds its shape, and lands beautifully under a screw terminal: more metal in contact with the lug, nothing to splay out, and no chance of a stray strand sitting outside the clamp.
Use solid for short, straight runs and for devices you are backwiring or screw-terminating — receptacles, switches, panel breakers on a tidy job. Avoid it for long conduit pulls with several bends, or anywhere the conductor will be flexed or vibrated; solid work-hardens and eventually breaks where stranded just bends. We stock the stranded version in the same gauge and colors if that suits the run better.
What Black Means
In black, this conductor is an ungrounded conductor — a hot. Black is the default first hot on every system.
Only white, grey and green are actually reserved by the NEC. The rest is convention — but convention is how the next electrician reads your panel at two in the morning, so pick a scheme and keep it across the whole job.
Ampacity: the Number You Can Actually Use
12 AWG copper carries 30 amps at 90°C by NEC Table 310.16 — and you will almost never get to use that figure.
NEC 110.14(C) derates the whole circuit to the lowest-rated termination in it, and breakers and lugs in ordinary gear are listed at 75°C. So the working number for this wire is normally 25 amps, and NEC 240.4(D) then caps the breaker at 20 amps for a conductor this size no matter what the table says.
| 60°C column | 20 A |
|---|---|
| 75°C column — typical real limit | 25 A |
| 90°C column | 30 A |
| NEC 240.4(D) breaker cap | 20 A |
Then two things take ampacity back off you:
- Conduit fill. More than three current-carrying conductors in a raceway and NEC 310.15(C)(1) starts derating — 80 percent at 4 to 6 conductors, 70 percent at 7 to 9. Neutrals on a balanced multiwire circuit do not count; neutrals on a non-linear load do.
- Ambient heat. An attic in Texas is not 30°C. Table 310.15(B)(1) is the correction, and it bites hard above 40°C.
The 90°C rating is not wasted — it is the number you derate from, which is exactly why 90°C wire gets specified for hot and crowded runs. If this is a feeder to a generator or transfer switch, the sizing rule is different again: see what size wire you need between a standby generator and a transfer switch, because NEC 445.13 adds its own 115 percent requirement.
Pulling It
Keep conduit fill inside NEC Chapter 9 Table 1 — 40 percent for three or more conductors — and use a proper lubricant on anything long or with more than a couple of bends. Roll-wound, so it feeds off the top without birdcaging. Solid wire will fight you on a long pull with multiple bends — plan the pull boxes accordingly.
Specifications
| Manufacturer part | 11587358 |
|---|---|
| Brand | Southwire |
| Type | THHN / THWN-2 single conductor building wire |
| Size | 12 AWG |
| Conductor | Solid annealed copper |
| Insulation | PVC with nylon jacket |
| Color | Black |
| Voltage rating | 600 V |
| Temperature rating | 90°C dry, 90°C wet (THWN-2) |
| Ampacity at 75°C | 25 A |
| Length | 500 ft |
| Approvals | UL 83, UL 1063 |
| Permitted locations | Conduit and raceway, wet or dry |
Need this color in another gauge or another length? We stock the full Southwire THHN range — ask.
Why Buy Wire From ZapDaddy Supplies
- Licensed electricians answer the phone — if you are not sure what size you need, ask before you spend $120.00
- Full reels, not cut scraps — what you order is what ships, in the original Southwire packaging
- Wire, breakers, switchgear and generators in one place so the whole job ships together
- Straight answers on code — we will tell you what your inspector is going to ask
Ready to Order?
Add it to the cart to see your price. Copper moves daily and our cart price tracks it — the number in the cart is the number you pay.
Complete the job
-
Southwire 12 AWG Solid Copper THHN/THWN-2 Building Wire, Green — 500 ft
$145.00Add to cart for lowest price -
Southwire 12 AWG Solid Copper THHN/THWN-2 Building Wire, Red — 500 ft
$145.00Add to cart for lowest price -
Southwire 12 AWG Solid Copper THHN/THWN-2 Building Wire, White — 500 ft
$145.00Add to cart for lowest price -
Southwire 12 AWG Stranded Copper THHN/THWN-2 Building Wire, Black — 500 ft
$150.00Add to cart for lowest price
Compare similar models
-
Southwire 12 AWG Solid Copper THHN/THWN-2 Building Wire, Green — 500 ft
$145.00Add to cart for lowest price -
Southwire 12 AWG Solid Copper THHN/THWN-2 Building Wire, Red — 500 ft
$145.00Add to cart for lowest price -
Southwire 12 AWG Solid Copper THHN/THWN-2 Building Wire, White — 500 ft
$145.00Add to cart for lowest price -
Southwire 12 AWG Stranded Copper THHN/THWN-2 Building Wire, Brown — 500 ft
$150.00Add to cart for lowest price -
Southwire 12 AWG Stranded Copper THHN/THWN-2 Building Wire, Yellow — 500 ft
$150.00Add to cart for lowest price -
Southwire 12 AWG Stranded Copper THHN/THWN-2 Building Wire, Green — 500 ft
$150.00Add to cart for lowest price -
Southwire 12 AWG Stranded Copper THHN/THWN-2 Building Wire, Blue — 500 ft
$150.00Add to cart for lowest price -
Southwire 12 AWG Stranded Copper THHN/THWN-2 Building Wire, Red — 500 ft
$150.00Add to cart for lowest price