The breaker exists to protect the wire, not the appliance. Its job is to open before the conductor overheats. Everything about sizing follows from that one idea.
The chart
| Copper wire | Standard breaker | Typical use |
|---|---|---|
| 14 AWG | 15 A | Lighting, bedroom receptacles |
| 12 AWG | 20 A | Kitchen, bath, laundry, garage |
| 10 AWG | 30 A | Water heater, dryer, small AC |
| 8 AWG | 40–50 A | Range, EV charger, subpanel |
| 6 AWG | 55–65 A | Large range, spa, 60 A subpanel |
| 4 AWG | 70–85 A | Subpanel |
| 3 AWG | 85–100 A | 100 A subpanel |
| 2 AWG | 95–115 A | 100 A subpanel with margin |
| 1/0 AWG | 125–150 A | Large feeder |
Why 14, 12 and 10 AWG have a hard cap
Those three sizes are capped by NEC 240.4(D) regardless of what the ampacity table says. 12 AWG carries 25 amps at 75°C, but you may not put it on a 25 amp breaker — 20 amps is the maximum, full stop.
| Size | Ampacity at 75°C | Maximum breaker |
|---|---|---|
| 14 AWG | 20 A | 15 A |
| 12 AWG | 25 A | 20 A |
| 10 AWG | 35 A | 30 A |
This exists because small conductors are the ones most likely to be damaged, spliced badly or extended by a homeowner. The cap gives them a safety margin the bigger sizes do not need.
The 75°C rule that sets everything else
THHN/THWN-2 is rated 90°C and you will rarely use that column. NEC 110.14(C) sizes the circuit to the lowest-rated termination, and breakers and lugs in residential gear are listed at 75°C.
So read the 75°C column. The 90°C column is what you derate from when conduit fill or ambient heat apply.
Three exceptions worth knowing
1. Air conditioners and motors
A condenser nameplate gives MCA and MOCP, and the MOCP is usually larger than the wire ampacity. A 40 amp breaker on 10 AWG is correct for an AC circuit when the nameplate says so — NEC 440.22 permits it, because the compressor has its own overload protection and needs inrush headroom.
2. Continuous loads go the other way
EV chargers, spa heaters and anything running three hours or more at full current must be sized at 125% under NEC 210.19(A)(1). A 48 amp charger needs a 60 amp circuit and 6 AWG — not the 50 amp you might expect.
3. The next-size-up rule
NEC 240.4(B) permits rounding up to the next standard breaker where the conductor ampacity does not land on a standard size — provided the circuit supplies no receptacles and is 800 amps or less. This does not override the 240.4(D) cap on 14, 12 and 10 AWG.
The mistake that actually matters
Never fit a bigger breaker to stop nuisance tripping. A breaker that keeps tripping is reporting a real condition — too much load, or a fault. Replacing a 15 amp breaker with a 20 on 14 AWG wire removes the protection and leaves the wire to overheat inside a wall.
If a breaker trips repeatedly, the answer is to move load to another circuit, or to run a new circuit in the correct gauge.
We stock Southwire THHN/THWN-2, NM-B Romex and UF-B in every common gauge.
Frequently Asked Questions
What size breaker for 12 gauge wire?
20 amps maximum. 12 AWG copper carries 25 amps at 75°C, but NEC 240.4(D) caps the overcurrent device at 20 amps for 12 AWG regardless.
Can I put a 30 amp breaker on 12 gauge wire?
No. NEC 240.4(D) limits 12 AWG to a 20 amp breaker. A 30 amp breaker on 12 AWG leaves the conductor unprotected and is a fire risk.
Why is my AC breaker bigger than the wire rating?
Air conditioning circuits are an exception. NEC 440.22 allows the overcurrent device to exceed the conductor ampacity up to the nameplate MOCP, because the compressor has its own overload protection and needs starting headroom.