What Size Wire for a 4-Ton Central AC?

Tonnage is a cooling capacity. Wire is sized from electrical current. The two are related but not interchangeable, which is why tonnage-to-wire charts are wrong in principle — two different 4-ton condensers can need different conductors.

The number that governs is on the data plate on the side of the outdoor unit.

MCA and MOCP

  • MCA — Minimum Circuit Ampacity. The smallest conductor ampacity the manufacturer permits.
  • MOCP — Maximum Overcurrent Protection. The largest breaker or fuse allowed, usually larger than the MCA.

That MOCP being bigger than the wire ampacity is normal and correct for air conditioning. A 45 amp breaker on 10 AWG is legitimate when the nameplate says so — NEC 440.22 permits it because the compressor carries its own overload protection and needs inrush headroom.

Typical 4-ton figures

Nameplate MCAMinimum copper wireTypical MOCP
Up to 25 A10 AWG35–45 A
26–30 A10 AWG40–50 A
31–35 A8 AWG45–60 A
36–40 A8 AWG50–60 A
Most residential 4-ton condensers land in the mid-to-high 20s, which is 10 AWG. High-efficiency and heat pump models can run higher.

So the usual answer is 10 AWG copper, with 8 AWG for higher-MCA units. Confirm against your nameplate before buying wire.

Heat pumps draw more

If the unit is a heat pump rather than a straight AC condenser, the MCA may include auxiliary or emergency strip heat, which changes everything. A heat pump with 10 kW of strip heat is a far bigger electrical load than a cooling-only condenser of the same tonnage.

Read the nameplate for the complete system, including any air handler heat kit, which is usually a separate circuit of its own.

What to run

  • Outdoors in conduit: individual 10 AWG THHN/THWN-2. The inside of outdoor conduit is a wet location by NEC 300.5(B), so you need the THWN-2 rating.
  • Indoors through framing: 10/2 NM-B — two hots and a ground, no neutral needed.
  • Buried without conduit: 10/2 UF-B.

You also need a disconnect within sight of the unit under NEC 440.14. Inspectors check it every time.

A 4-ton AC dominates generator sizing

If you are planning standby power, this is the load that decides your generator size. A 4-ton compressor draws roughly 4,800 watts running, and two to three times that for a second or two at startup.

That surge is usually what sets the generator, not the running total. Our sizing calculator shows running load and starting surge separately so you can see which one is driving your answer.

We stock Southwire THHN/THWN-2, NM-B Romex and UF-B direct burial in every common gauge.

Frequently Asked Questions

What size wire for a 4-ton AC unit?

Usually 10 AWG copper. Most residential 4-ton condensers have a nameplate MCA in the mid-to-high 20s. Higher-MCA units need 8 AWG. Always size from the MCA on the data plate, not from tonnage.

Can I use a 45 amp breaker on 10 AWG for an AC?

Yes, if the nameplate MOCP permits it. NEC 440.22 allows the overcurrent device to exceed conductor ampacity for motor-compressor circuits. This exception applies only to air conditioning and motor loads.

Does a heat pump need bigger wire than an AC?

Often yes. A heat pump’s MCA may include auxiliary or emergency strip heat, which is a much larger load. Read the nameplate for the complete system including any air handler heat kit.