A 60 amp subpanel is the usual answer for a garage, workshop or detached building. The wire part is straightforward. The part that fails inspections is what happens inside the panel when you get there.
The wire
6 AWG copper, which carries 65 amps at 75°C — comfortably above 60. In aluminium you would need 4 AWG.
You need four conductors, not three:
- Two hots
- One neutral
- One equipment ground
| Copper size | 60°C | 75°C | 90°C | Breaker cap (240.4(D)) |
|---|---|---|---|---|
| 14 AWG | 15 A | 20 A | 25 A | 15 A |
| 12 AWG | 20 A | 25 A | 30 A | 20 A |
| 10 AWG | 30 A | 35 A | 40 A | 30 A |
| 8 AWG | 40 A | 50 A | 55 A | — |
| 6 AWG | 55 A | 65 A | 75 A | — |
| 4 AWG | 70 A | 85 A | 95 A | — |
| 3 AWG | 85 A | 100 A | 115 A | — |
| 2 AWG | 95 A | 115 A | 130 A | — |
The rule that fails inspections
In a subpanel, the neutral bar and the ground bar must be separated. The neutral bar is isolated from the enclosure; the ground bar is bonded to it. The bonding screw or strap that comes fitted in a new panel must be removed.
They are only joined at the service — your main panel — and nowhere else. If they are joined again downstream, normal neutral current starts flowing on the grounding conductor and on any metal path connecting the two buildings. That is a genuine shock hazard, and it is the single most common error on a subpanel install.
This is why you run four wires and not three. Three-wire feeders to outbuildings were permitted under older code and are not any longer.
What to run
- In conduit: individual 6 AWG THHN/THWN-2 conductors. Outdoors or underground, the inside of the conduit is a wet location, so THWN-2 is required.
- Through framing indoors: 6/3 NM-B with ground gives you exactly the four conductors you need.
- Buried direct to a detached building: UF-B, or conduit with THWN-2.
Detached buildings have extra requirements
- A disconnecting means at the detached building (NEC 225.31) — usually the subpanel’s own main breaker.
- A grounding electrode at the detached building (NEC 250.32) — typically one or two ground rods, bonded to the subpanel’s ground bar. The ground rod does not replace the equipment grounding conductor in the feeder; you need both.
- Burial depth per NEC Table 300.5 — generally 24 inches direct burial, 18 inches in conduit.
Is 60 amps enough?
For lighting, receptacles, a compressor and ordinary hand tools, comfortably. If you are adding a welder, a large dust collector, an EV charger or electric heat, work out the actual load first — stepping up to a 100 amp feeder is far cheaper now than digging the trench twice.
And check the run length. At 60 amps and 240 volts, 6 AWG holds its voltage well past 100 feet, but a 200 foot run to a back-of-property shop wants 4 AWG. See wire size for a 100 foot run.
We stock Southwire THHN/THWN-2 building wire, NM-B Romex and UF-B direct burial cable in every common gauge. Not sure which you need? Tell us the run and the load and a licensed electrician will size it with you.
Frequently Asked Questions
What size wire do I need for a 60 amp subpanel?
6 AWG copper, or 4 AWG aluminium. You need four conductors — two hots, a neutral and a separate equipment ground.
Can I use 6/3 Romex for a 60 amp subpanel?
Yes, indoors in dry locations. 6/3 NM-B with ground gives the two hots, neutral and ground you need. It cannot be used outdoors, underground, or in wet locations.
Do I need to separate the neutral and ground in a subpanel?
Yes, always. The bonding screw must be removed so the neutral bar is isolated from the enclosure. Neutral and ground are bonded only at the service, never downstream.