What Size Wire for a 60 Amp Subpanel in a Garage or Shop?

A 60 amp subpanel is the usual answer for a garage, workshop or detached building. The wire part is straightforward. The part that fails inspections is what happens inside the panel when you get there.

The wire

6 AWG copper, which carries 65 amps at 75°C — comfortably above 60. In aluminium you would need 4 AWG.

You need four conductors, not three:

  • Two hots
  • One neutral
  • One equipment ground
Copper size60°C75°C90°CBreaker cap (240.4(D))
14 AWG15 A20 A25 A15 A
12 AWG20 A25 A30 A20 A
10 AWG30 A35 A40 A30 A
8 AWG40 A50 A55 A—
6 AWG55 A65 A75 A—
4 AWG70 A85 A95 A—
3 AWG85 A100 A115 A—
2 AWG95 A115 A130 A—
NEC Table 310.16, copper, not more than three current-carrying conductors. NEC 240.4(D) caps the overcurrent device on 14, 12 and 10 AWG regardless of the ampacity shown.

The rule that fails inspections

In a subpanel, the neutral bar and the ground bar must be separated. The neutral bar is isolated from the enclosure; the ground bar is bonded to it. The bonding screw or strap that comes fitted in a new panel must be removed.

They are only joined at the service — your main panel — and nowhere else. If they are joined again downstream, normal neutral current starts flowing on the grounding conductor and on any metal path connecting the two buildings. That is a genuine shock hazard, and it is the single most common error on a subpanel install.

This is why you run four wires and not three. Three-wire feeders to outbuildings were permitted under older code and are not any longer.

What to run

  • In conduit: individual 6 AWG THHN/THWN-2 conductors. Outdoors or underground, the inside of the conduit is a wet location, so THWN-2 is required.
  • Through framing indoors: 6/3 NM-B with ground gives you exactly the four conductors you need.
  • Buried direct to a detached building: UF-B, or conduit with THWN-2.

Detached buildings have extra requirements

  • A disconnecting means at the detached building (NEC 225.31) — usually the subpanel’s own main breaker.
  • A grounding electrode at the detached building (NEC 250.32) — typically one or two ground rods, bonded to the subpanel’s ground bar. The ground rod does not replace the equipment grounding conductor in the feeder; you need both.
  • Burial depth per NEC Table 300.5 — generally 24 inches direct burial, 18 inches in conduit.

Is 60 amps enough?

For lighting, receptacles, a compressor and ordinary hand tools, comfortably. If you are adding a welder, a large dust collector, an EV charger or electric heat, work out the actual load first — stepping up to a 100 amp feeder is far cheaper now than digging the trench twice.

And check the run length. At 60 amps and 240 volts, 6 AWG holds its voltage well past 100 feet, but a 200 foot run to a back-of-property shop wants 4 AWG. See wire size for a 100 foot run.

We stock Southwire THHN/THWN-2 building wire, NM-B Romex and UF-B direct burial cable in every common gauge. Not sure which you need? Tell us the run and the load and a licensed electrician will size it with you.

Frequently Asked Questions

What size wire do I need for a 60 amp subpanel?

6 AWG copper, or 4 AWG aluminium. You need four conductors — two hots, a neutral and a separate equipment ground.

Can I use 6/3 Romex for a 60 amp subpanel?

Yes, indoors in dry locations. 6/3 NM-B with ground gives the two hots, neutral and ground you need. It cannot be used outdoors, underground, or in wet locations.

Do I need to separate the neutral and ground in a subpanel?

Yes, always. The bonding screw must be removed so the neutral bar is isolated from the enclosure. Neutral and ground are bonded only at the service, never downstream.