An electric dryer is one of the most standardised circuits in a house: 30 amps, 10 AWG copper, four conductors. The part that catches people is the fourth wire, particularly in an older home.
The short answer
| Requirement | |
|---|---|
| Circuit | 30 A, 240 V |
| Wire | 10 AWG copper |
| Cable | 10/3 NM-B with ground |
| Conductors | Two hots, neutral, ground |
| Receptacle | NEMA 14-30 |
A dryer needs 240 V for the heating element and 120 V for the motor, timer and controls — which is why it needs a neutral and a ground, not one doing both jobs.
Three-wire vs four-wire, and why it changed
Before the 1996 NEC, dryers were allowed a three-wire connection — two hots and a combined neutral/ground — using a NEMA 10-30 receptacle. The appliance frame was bonded to the neutral.
That is no longer permitted for new work, because if the neutral is ever lost the dryer’s metal case can become energised. The four-wire NEMA 14-30 separates the functions.
- Existing 3-wire installations may remain under NEC 250.140. You are not required to rewire a working one.
- Any new circuit must be four-wire.
- If you replace the receptacle, you replace the circuit — you cannot fit a 14-30 to a three-wire cable and call it done. There is no legitimate way to get a safe ground out of three conductors.
A new dryer in an old house with a 10-30 outlet gives you two legitimate options: fit the matching three-wire cord to the new dryer, or run a new four-wire circuit. Do not use an adapter.
Why 10 AWG and not something smaller
10 AWG copper carries 30 amps at 60°C, which is what NEC 334.80 requires for NM-B. NEC 240.4(D) caps the breaker at 30 amps for 10 AWG, which matches the circuit exactly.
NEC 220.54 lets you calculate a dryer at 5,000 watts or nameplate, whichever is greater, for service load purposes — but the branch circuit itself is a straightforward 30 amps.
Gas dryers are different
A gas dryer only needs 120 V for the motor, drum light and controls. That is an ordinary 15 or 20 amp circuit on 14 or 12 AWG — no 240 V, no 30 amp breaker, no four-wire cable.
If you are switching from electric to gas, the 30 amp circuit becomes spare. Do not leave a 30 amp breaker feeding a 120 V receptacle.
What to run
- Through framing indoors: 10/3 NM-B with ground — pink jacket, which is the colour code for three-conductor 10 AWG.
- In conduit: individual 10 AWG THHN/THWN-2 conductors.
We stock Southwire THHN/THWN-2, NM-B Romex and UF-B in every common gauge.
Frequently Asked Questions
What size wire do I need for an electric dryer?
10 AWG copper on a 30 amp breaker, with four conductors — two hots, a neutral and a ground. 10/3 NM-B with ground is the usual cable.
Can I use a 3-prong dryer outlet?
Existing three-wire installations may remain in service under NEC 250.140, but any new circuit must be four-wire. If you replace the receptacle you must replace the circuit — adapters are not a safe solution.
Why does a dryer need a neutral and a ground?
The heating element runs on 240 V across the two hots, while the motor, timer and controls run on 120 V, which needs a neutral. The ground is a separate safety path for the appliance frame.