12/2 and 12/3 are the same 12 AWG copper, the same 20 amp capability and the same installation rules. The difference is one conductor — and that conductor solves four specific problems.
What is actually in each
| 12/2 with ground | 12/3 with ground | |
|---|---|---|
| Insulated conductors | Black, white | Black, red, white |
| Ground | Bare copper | Bare copper |
| Jacket colour | Yellow | Purple |
| Amperage | 20 A | 20 A |
| Typical use | Standard circuits | Three-way, MWBC, 240 V with neutral |
Note the jacket colour. People assume yellow means 12 AWG and that is only half true — 12/2 is yellow but 12/3 is purple. Likewise 14/2 is white while 14/3 is blue, and 10/2 is orange while 10/3 is pink.
Four reasons to use 12/3
1. Three-way switches
Controlling one light from two places needs a traveller between the switches. The red conductor is that traveller. This is the most common use of 12/3 in a house.
2. A multiwire branch circuit
Two 20 amp circuits sharing one neutral. Black on one phase, red on the other, white shared. You get two circuits down one cable instead of two.
Two rules if you do this. The two hots must be on opposite phases, or the shared neutral carries the sum of both currents instead of the difference — a fire risk. And NEC 210.4(B) requires a means of disconnecting both hots simultaneously, which in practice means a two-pole breaker or an approved handle tie.
3. A 240 volt load that needs a neutral
Some 240 V equipment needs 120 V for controls or a timer. Black and red give 240 V between them, white gives 120 V to either. Dryers are the classic case.
4. Switched and unswitched at the same outlet
Half a receptacle on a wall switch, half always live — a lamp controlled at the door with the other socket still usable.
When 12/2 is the right choice
Everywhere else, which is most places. Standard 20 amp kitchen, bathroom, laundry and garage circuits, single-switch lighting, individual appliance circuits. Do not pay for a conductor you will not terminate.
Both are 20 amp cable
12 AWG copper carries 20 amps at 60°C, which is the column NEC 334.80 requires for NM-B regardless of the 90°C insulation. NEC 240.4(D) caps the breaker at 20 amps either way. The third conductor adds capability, not capacity.
And remember where NM-B can go
Dry, indoor, protected locations only. Not underground, not in wet or damp locations, not in conduit outdoors. That is what UF-B and THWN-2 are for.
We stock NM-B Romex in 14 AWG through 6 AWG, two and three conductor, from 50 ft to 1,000 ft.
We stock Southwire THHN/THWN-2, NM-B Romex, UF-B direct burial and MC cable. Tell us the load and the run length and a licensed electrician will size it with you before you order.
Frequently Asked Questions
What is the difference between 12/2 and 12/3 Romex?
12/3 has an extra red conductor. Both are 12 AWG and both carry 20 amps. The red is used for three-way switch travellers, multiwire branch circuits, 240 V loads needing a neutral, or switched-plus-unswitched outlets.
What colour is 12/3 Romex?
Purple. Only two-conductor NM-B follows the familiar gauge colours — 12/2 is yellow, but 12/3 is purple, 14/3 is blue and 10/3 is pink.
Can I use 12/3 instead of 12/2?
Yes, it is electrically fine — simply cap the unused red conductor at both ends. But it costs more, so there is no reason unless you have it on hand or expect to use the third conductor later.