Almost every answer to this question gives you a chart from tonnage to wire gauge. Those charts are wrong in principle, because tonnage is a cooling capacity and wire is sized from electrical current. Two different 3-ton condensers can need different wire.
The number that actually governs is printed on the data plate on the side of the outdoor unit.
The two numbers on the nameplate
- MCA — Minimum Circuit Ampacity. The smallest conductor ampacity the manufacturer permits. Your wire must carry at least this.
- MOCP — Maximum Overcurrent Protection. The largest breaker or fuse allowed. Usually larger than the MCA, because the compressor needs inrush headroom.
That MOCP being larger than MCA is why air conditioning is an exception to the usual “breaker matches wire” habit. It is entirely normal and correct to have a 40 amp breaker on 10 AWG wire for an AC condenser, if that is what the nameplate calls for. NEC 440.22 permits it; the compressor’s own overload protection handles the rest.
Typical 3-ton figures
| Nameplate MCA | Minimum copper wire | Typical MOCP |
|---|---|---|
| Up to 20 A | 12 AWG | 25–30 A |
| 21–25 A | 10 AWG | 30–40 A |
| 26–30 A | 10 AWG | 40–45 A |
| 31–35 A | 8 AWG | 45–50 A |
So the usual answer for a 3-ton system is 10 AWG copper — but confirm it against your nameplate before you buy wire.
| Copper size | 60°C | 75°C | 90°C | Breaker cap (240.4(D)) |
|---|---|---|---|---|
| 14 AWG | 15 A | 20 A | 25 A | 15 A |
| 12 AWG | 20 A | 25 A | 30 A | 20 A |
| 10 AWG | 30 A | 35 A | 40 A | 30 A |
| 8 AWG | 40 A | 50 A | 55 A | — |
| 6 AWG | 55 A | 65 A | 75 A | — |
| 4 AWG | 70 A | 85 A | 95 A | — |
| 3 AWG | 85 A | 100 A | 115 A | — |
| 2 AWG | 95 A | 115 A | 130 A | — |
The 75°C rule that decides everything
THHN/THWN-2 is rated 90°C, and you will almost never get to use that column. NEC 110.14(C) requires the circuit to be sized to the lowest-rated termination, and breakers and lugs in ordinary residential gear are listed at 75°C.
So the 75°C column is your working number. The 90°C column is what you derate from when conduit fill or high ambient temperature apply — which is exactly why 90°C wire is specified for hot attics and crowded raceways.
What to actually run
- Outdoors in conduit: individual 10 AWG THHN/THWN-2 conductors. The inside of outdoor conduit is a wet location by NEC 300.5(B), so you need the THWN-2 rating, not plain THHN.
- Indoors through framing: 10/2 NM-B is usual for a 240 V condenser, which needs two hots and a ground but no neutral.
- Buried without conduit: 10/2 UF-B.
You will also need a disconnect within sight of the unit — NEC 440.14 requires it, and the inspector will check.
When to go up a size
Ampacity is not the only constraint. On a long run, voltage drop can force a larger conductor than the table requires. A compressor fed at low voltage draws more current, runs hotter and dies younger.
Past about 100 feet it is worth checking. Our guide on wire size for a 100 foot run covers the arithmetic.
We stock Southwire THHN/THWN-2 building wire, NM-B Romex and UF-B direct burial cable in every common gauge. Not sure which you need? Tell us the run and the load and a licensed electrician will size it with you.
Frequently Asked Questions
What size wire do I need for a 3-ton AC unit?
Most residential 3-ton condensers have a nameplate MCA in the low-to-mid 20s, which calls for 10 AWG copper. Always confirm against the MCA on your unit’s data plate rather than sizing from tonnage.
Can I use a 40 amp breaker on 10 AWG wire for an AC?
For an air conditioning condenser, yes, if the nameplate MOCP permits it. NEC 440.22 allows the overcurrent device to exceed the conductor ampacity for motor-compressor circuits. This is not permitted for ordinary branch circuits.
Do I need a neutral for an air conditioner?
Usually not. A 240 V condenser needs two hots and an equipment ground, which is why 10/2 NM-B with ground is the common choice indoors.