What Size Wire for a Level 2 EV Charger? 32A, 40A and 48A

EV charging is different from almost everything else in a house because it is a continuous load — three hours or more at full current. NEC 625.41 requires the circuit to be sized at 125% of the charger’s rated current, and that is what decides the wire.

The three common sizes

Charger outputCircuit size (125%)Minimum copper wireTypical use
32 A40 A breaker8 AWGmost plug-in chargers, NEMA 14-50
40 A50 A breaker8 AWGcommon hardwired
48 A60 A breaker6 AWGmaximum for most home units
Copper, 75°C termination rating. 8 AWG carries 50 A and 6 AWG carries 65 A at 75°C.

The 48 amp charger is the one people get wrong. 8 AWG is good for 50 amps and a 48 amp charger needs a 60 amp circuit — so it needs 6 AWG, not 8.

Copper size60°C75°C90°CBreaker cap (240.4(D))
14 AWG15 A20 A25 A15 A
12 AWG20 A25 A30 A20 A
10 AWG30 A35 A40 A30 A
8 AWG40 A50 A55 A—
6 AWG55 A65 A75 A—
4 AWG70 A85 A95 A—
3 AWG85 A100 A115 A—
2 AWG95 A115 A130 A—
NEC Table 310.16, copper, not more than three current-carrying conductors. NEC 240.4(D) caps the overcurrent device on 14, 12 and 10 AWG regardless of the ampacity shown.

The 75°C rule that decides everything

THHN/THWN-2 is rated 90°C, and you will almost never get to use that column. NEC 110.14(C) requires the circuit to be sized to the lowest-rated termination, and breakers and lugs in ordinary residential gear are listed at 75°C.

So the 75°C column is your working number. The 90°C column is what you derate from when conduit fill or high ambient temperature apply — which is exactly why 90°C wire is specified for hot attics and crowded raceways.

What to run where

  • Garage wall, in conduit: individual 6 AWG THHN/THWN-2 conductors — two hots, a ground, and a neutral only if your charger needs one (most hardwired units do not).
  • Through framing: 6/3 NM-B if you need a neutral, 6/2 if you do not.
  • Out to a detached garage underground: UF-B or conduit with THWN-2.

Hardwired or plug-in?

A NEMA 14-50 receptacle is convenient and lets you take the charger with you. But note that a receptacle on a 50 amp circuit limits you to a 40 amp charger — and NEC 625.44 has specific requirements for cord-and-plug EVSE.

Hardwiring is what you want for 48 amps, and it removes the receptacle as a failure point. Loose connections in a 14-50 under continuous load are a well-documented cause of overheating.

Before you size the wire, check the panel

A 60 amp continuous circuit is a substantial addition. Two things to confirm:

  1. Is there physical space for a two-pole breaker?
  2. Does your service have capacity? NEC 220.83 covers adding a load to an existing dwelling. On a 100 amp service with electric heat or an electric range, a 48 amp charger may not fit without load management or a service upgrade.

Many chargers now offer adjustable current or load sharing, which is often cheaper than upgrading the service.

Do not forget GFCI

NEC 625.54 requires GFCI protection for receptacle-connected EVSE at 150 V to ground or less and 50 amps or less. Requirements have tightened across recent code cycles and your jurisdiction may be on a different edition — ask your inspector which code year applies before you buy the breaker.

We stock Southwire THHN/THWN-2 building wire, NM-B Romex and UF-B direct burial cable in every common gauge. Not sure which you need? Tell us the run and the load and a licensed electrician will size it with you.

Frequently Asked Questions

What size wire for a 48 amp EV charger?

6 AWG copper on a 60 amp breaker. A 48 amp charger is a continuous load, so NEC 625.41 requires the circuit to be sized at 125% — that is 60 amps, which is beyond 8 AWG.

Can I use 8 AWG wire for an EV charger?

Yes for a 32 amp or 40 amp charger, on a 40 or 50 amp breaker respectively. Not for a 48 amp charger, which needs 6 AWG.

Why is the breaker bigger than the charger current?

EV charging is a continuous load. NEC requires continuous loads to be sized at 125% of the current, so a 40 amp charger needs a 50 amp circuit.