EV charging is different from almost everything else in a house because it is a continuous load — three hours or more at full current. NEC 625.41 requires the circuit to be sized at 125% of the charger’s rated current, and that is what decides the wire.
The three common sizes
| Charger output | Circuit size (125%) | Minimum copper wire | Typical use |
|---|---|---|---|
| 32 A | 40 A breaker | 8 AWG | most plug-in chargers, NEMA 14-50 |
| 40 A | 50 A breaker | 8 AWG | common hardwired |
| 48 A | 60 A breaker | 6 AWG | maximum for most home units |
The 48 amp charger is the one people get wrong. 8 AWG is good for 50 amps and a 48 amp charger needs a 60 amp circuit — so it needs 6 AWG, not 8.
| Copper size | 60°C | 75°C | 90°C | Breaker cap (240.4(D)) |
|---|---|---|---|---|
| 14 AWG | 15 A | 20 A | 25 A | 15 A |
| 12 AWG | 20 A | 25 A | 30 A | 20 A |
| 10 AWG | 30 A | 35 A | 40 A | 30 A |
| 8 AWG | 40 A | 50 A | 55 A | — |
| 6 AWG | 55 A | 65 A | 75 A | — |
| 4 AWG | 70 A | 85 A | 95 A | — |
| 3 AWG | 85 A | 100 A | 115 A | — |
| 2 AWG | 95 A | 115 A | 130 A | — |
The 75°C rule that decides everything
THHN/THWN-2 is rated 90°C, and you will almost never get to use that column. NEC 110.14(C) requires the circuit to be sized to the lowest-rated termination, and breakers and lugs in ordinary residential gear are listed at 75°C.
So the 75°C column is your working number. The 90°C column is what you derate from when conduit fill or high ambient temperature apply — which is exactly why 90°C wire is specified for hot attics and crowded raceways.
What to run where
- Garage wall, in conduit: individual 6 AWG THHN/THWN-2 conductors — two hots, a ground, and a neutral only if your charger needs one (most hardwired units do not).
- Through framing: 6/3 NM-B if you need a neutral, 6/2 if you do not.
- Out to a detached garage underground: UF-B or conduit with THWN-2.
Hardwired or plug-in?
A NEMA 14-50 receptacle is convenient and lets you take the charger with you. But note that a receptacle on a 50 amp circuit limits you to a 40 amp charger — and NEC 625.44 has specific requirements for cord-and-plug EVSE.
Hardwiring is what you want for 48 amps, and it removes the receptacle as a failure point. Loose connections in a 14-50 under continuous load are a well-documented cause of overheating.
Before you size the wire, check the panel
A 60 amp continuous circuit is a substantial addition. Two things to confirm:
- Is there physical space for a two-pole breaker?
- Does your service have capacity? NEC 220.83 covers adding a load to an existing dwelling. On a 100 amp service with electric heat or an electric range, a 48 amp charger may not fit without load management or a service upgrade.
Many chargers now offer adjustable current or load sharing, which is often cheaper than upgrading the service.
Do not forget GFCI
NEC 625.54 requires GFCI protection for receptacle-connected EVSE at 150 V to ground or less and 50 amps or less. Requirements have tightened across recent code cycles and your jurisdiction may be on a different edition — ask your inspector which code year applies before you buy the breaker.
We stock Southwire THHN/THWN-2 building wire, NM-B Romex and UF-B direct burial cable in every common gauge. Not sure which you need? Tell us the run and the load and a licensed electrician will size it with you.
Frequently Asked Questions
What size wire for a 48 amp EV charger?
6 AWG copper on a 60 amp breaker. A 48 amp charger is a continuous load, so NEC 625.41 requires the circuit to be sized at 125% — that is 60 amps, which is beyond 8 AWG.
Can I use 8 AWG wire for an EV charger?
Yes for a 32 amp or 40 amp charger, on a 40 or 50 amp breaker respectively. Not for a 48 amp charger, which needs 6 AWG.
Why is the breaker bigger than the charger current?
EV charging is a continuous load. NEC requires continuous loads to be sized at 125% of the current, so a 40 amp charger needs a 50 amp circuit.