Can You Use THHN Outdoors or Underground? The THWN-2 Distinction

This is one of the most common code violations in residential work, and it happens because two very similar markings mean very different things.

What the markings mean

MarkingDry locationsWet locations
THHN90°Cnot rated
THWN75°C75°C
THWN-290°C90°C
THWN-2 is what you want. Most building wire sold today is dual-marked THHN/THWN-2.

Plain THHN is rated for dry locations only. If the jacket says only THHN, it does not belong outdoors, in outdoor conduit, or underground.

The part that surprises people

The inside of a conduit run outdoors or underground is a wet location. Not damp — wet. NEC 300.5(B) states that the interior of an underground raceway is a wet location, and 300.9 says the same for raceways in wet locations above ground.

It does not matter that the conduit is sealed. Condensation forms inside from temperature cycling, and water finds its way in through fittings and ends. Code assumes it will be wet because in practice it is.

So the buried PVC from your house to the garage, and the rigid conduit running down an exterior wall, both need THWN-2.

How to check what you have

Read the printing on the insulation. It is stamped repeatedly along the length. You are looking for THWN-2 to appear. If you see only THHN, it is dry-rated.

In practice almost all building wire manufactured today is dual-rated and the stamp reads something like THHN/THWN-2. But “almost all” is not “all”, and older stock on a shelf may not be. Check before you pull 200 feet of it into a trench.

What about NM-B and UF-B?

  • NM-B (Romex) — dry, indoor, protected locations only. Never outdoors, never underground, never in wet locations, and not in outdoor conduit either.
  • UF-B — rated for direct burial and sunlight. This is the cable for going underground without conduit. It still needs physical protection where it emerges and runs up a wall.
  • THWN-2 in conduit — the usual approach for anything substantial going outside or underground.

The other half of the question: sunlight

Conductors exposed to sunlight need to be marked sunlight resistant. Inside conduit this is not an issue, but it matters for cable runs on an exterior surface. UF-B is sunlight resistant; check the marking on anything else.

Why 90°C matters even when you cannot use it

NEC 110.14(C) pulls your circuit back to the 75°C termination rating in ordinary gear, so the 90°C column is rarely your working number.

It is still worth having. The 90°C rating is the figure you derate from when conduit fill or high ambient temperature apply — and in a hot attic or a crowded raceway, starting from 90°C rather than 75°C can be the difference between one conductor size and the next.

We stock Southwire THHN/THWN-2 building wire in 12 through 6 AWG, solid and stranded, in every standard colour.

We stock Southwire THHN/THWN-2, NM-B Romex, UF-B direct burial and MC cable. Tell us the load and the run length and a licensed electrician will size it with you before you order.

Frequently Asked Questions

Can THHN wire be used outside?

Only if it is dual-rated THWN-2, which nearly all modern building wire is. Plain THHN is rated for dry locations only. Check the printing on the insulation.

Is the inside of underground conduit a wet location?

Yes. NEC 300.5(B) classifies the interior of an underground raceway as a wet location, regardless of how well sealed it is. Conductors there must be rated for wet locations.

Can I run Romex in conduit outside?

No. NM-B is for dry, indoor, protected locations only. Putting it in conduit does not change that. Use THWN-2 in conduit, or UF-B for direct burial.