A standby generator that will not start during an outage is a sickening moment. The good news is that the cause is usually one of six things, and the first one accounts for most of them.
1. The battery — this is most of them
Ask anyone who services these for a living: the overwhelming majority of no-start calls are the battery, not the engine.
The reason it catches people is that the weekly exercise cycle takes almost nothing out of a battery. It tests fine for years, right up until it is asked for real cranking current — usually in the cold, when its capacity is already reduced.
- Age is the test. Standby batteries last three to four years. If yours is older than that, it is the suspect regardless of how it looks.
- Listen when it tries. Rapid clicking or slow laboured cranking is a battery. Silence is more likely a controller or a fuse.
- Check the terminals for corrosion and tightness.
In a cold climate a battery heater keeps it able to deliver current when it matters.
2. It is not in AUTO
Embarrassing and extremely common. The controller has OFF, MANUAL and AUTO. If someone set it to OFF for a service and never set it back, it will sit there through the entire outage doing nothing.
Check the controller first. It takes five seconds and it is free.
3. The fuel valve is closed
Also commonly left shut after service or after work on the gas line. Follow the pipe from the meter to the unit and confirm the valve is open.
On propane, check the tank. A tank that read a quarter full in October may be empty by February, and suppliers do not deliver during the storm that caused your outage.
4. Low oil shutdown
Every standby generator has a low-oil sensor that prevents it starting rather than letting it destroy itself. Air-cooled engines consume oil, particularly if they have run a long outage recently.
Check the dipstick. If it is low, top it up with the specified oil and try again. If it is low and you have not run it much, you may have a leak worth investigating.
5. A tripped breaker or blown fuse
There is usually a main line circuit breaker on the generator itself, and a small fuse in the controller circuit. Both can trip or blow. Check the generator’s own breaker as well as your panel.
6. Cold
Below freezing, oil thickens and battery capacity drops at the same time — demand rises exactly as supply falls. A unit that started fine in October can fail in January with nothing actually broken.
If this is a recurring winter problem, fit a cold weather kit. The oil heater and battery warmer solve the two halves separately and are designed to be used together.
What to check, in order
- Is the controller in AUTO?
- Is the gas valve open? Is there fuel in the propane tank?
- Is the oil level correct?
- Is the generator’s own main breaker on?
- How old is the battery? Over three years, suspect it.
- Is there a fault code on the controller? Note it before clearing it.
The fix that prevents all of this
Do not disable the weekly exercise cycle. It is the only thing that surfaces these faults while you can still do something about them. If the noise bothers you, change the day and time rather than switching it off.
And service it annually. See how often to service a standby generator — the annual visit is when the battery gets tested and the rodent damage gets found.
Frequently Asked Questions
Why does my Generac not start during a power outage?
Most commonly a dead battery, which tests fine during weekly exercise but cannot deliver cranking current when needed. Also check that the controller is in AUTO, the gas valve is open, and the oil level is correct.
How long do standby generator batteries last?
Three to four years. They rarely warn you, because the weekly exercise cycle draws almost nothing — replace on age rather than waiting for symptoms.
My generator clicks but will not crank. What is wrong?
Rapid clicking almost always means insufficient battery power to turn the starter. Check the battery age and terminal connections first.